Section 108. LIABILITY  


Appendix 109. CAR WASH REQUIREMENTS.
§ 109.01. GENERAL PROVISIONS.
§ 109.02. DEFINITIONS.
§ 109.03. CONVEYOR CAR WASH WATER RECYCLING REQUIREMENTS.
§ 922.1. MINIMUM NUMBER OF FIXTURES.
§ 922.2. SEPARATE FACILITIES.
§ 922.3. COMMON FACILITIES.
§ 925.1. GENERAL.
§ 925.2. APPLICATION TO RESIDENTIAL USE.
§ 925.3. APPLICATION TO NONRESIDENTIAL USES.
§ 925.4. EXTERIOR IRRIGATION & WATERING SYSTEMS.
§ 925.5. EFFECTIVE DATE.

This Code shall not be construed as imposing upon the municipal, county or state authority any liability or responsibility for damages to any person or property caused by any defect in any piping or appliance mentioned herein, or by installation thereof, nor shall the local governing body or any official or employee thereof, be held as assuming any such liability or responsibility by reason of the inspection authorized hereunder or the certificate of approval issued by the Inspector.

SECTION 2: That Section 202, Definition of Terms, be altered by adding the following definitions in their proper places, and that the definition on "Safe Waste System" be replaced as follows:

DIRECTOR: The Director of the Bureau of Buildings is the administrative authority to administer and enforce the provisions of this Code as adopted or amended.

SAFE WASTE SYSTEM: A horizontal waste system composed of main waste line, branch waste lines, auxiliary vents and a master trap with a fresh air vent. (See Section 1605 and Drawings A15, A16 and A17 of Appendix K.)

SECTION 3: That Section 404 entitled Trenching, Excavation and Backfill be amended by adding, Section 404.6 entitled Excavating and Trenching Safety, to read as follows:

"All excavations or trenching over 5 feet deep shall be sloped or supported and provided with an adequate means of exit, in accordance with Occupational Safety and Health Administration Federal Register 29CFR 1926.650, 1926.651 and 1926.652."

SECTION 4: That Section 504 entitled Limitations of use of materials listed in Table 500 be amended by deleting, Section 504.8.1 and substituting the following in lieu thereof:

"504.8.1 Approved air admittance valves may be permitted for installation in plumbing systems five branch intervals or less, with prior approval from the Director of the Bureau of Buildings, or his authorized representative. Such valves shall comply with ASSE 1051 listed in Table 500."

SECTION 5: That Chapter 9, entitled Plumbing Fixtures, be amended as follows:

1.

That Section 914.1.4 be deleted and the following substituted in lieu thereof:

"914.1.4 Floor drain trap seals subject to evaporation shall be fed from an approved plumbing fixture or by means of an approved automatic priming device designed and approved for that purpose."

2.

That a new Section 921.9 entitled Thermal Expansion, be added as follows:

921.9 Thermal Expansion.

(a) When water is heated in a distribution system or branch of the system that has been closed by the installation of a backflow preventer, a pressure reducing valve, or any other checking device, an approved auxiliary relief valve shall be installed at an accessible location downstream from the check device to limit thermal expansion of the heated water to not more than 80 psi no-flow pressure at any fixture on the system. A discharge line not less than ¼-inch inside diameter shall be piped to an approved location where no water damage would result from the discharge, and any water in the discharge pipe would drain by gravity, and be protected from freezing.

(b) The auxiliary relief valve shall be in addition to the water heater safety relief valve. This thermal expansion control device shall be designed and trimmed for repeated operation. The valve shall be a minimum ½-inch pipe size, shall be adjustable and calibrated, and shall include a tag describing its function. The maximum adjustable range of the thermal expansion valve shall be not more than 125 pounds (psi). The maximum setting of the calibrated relief valve shall provide not more than 80 pounds static (no-flow) pressure at any fixture in the system, but in no case shall the setting be less than 25 pounds below that of the water heater safety relief valve.

EXCEPTION: In lieu of the above auxiliary relief valve, an approved pre-charged expansion chamber that is permanently separated from the water may be used. The chamber shall have a rated working pressure not less than the pressure setting of the water heater safety relief valve, and a corresponding temperature rating not less than 210°F. The chamber shall have the capacity to limit thermal expansion to the above specified 80 psi maximum.